What is the leading ignition protection type for UHP pressure transducers?

The leading ignition protection type is crucial for the electrical connection of a pressure sensor with explosion protection. It does not necessarily must be the one with the stricter requirements. This applies, for instance, for the UHP pressure transducers of the WU series from WIKA. They are designed for use in semiconductor production.
Explosion protection can be an indispensable safety precaution there. This is due to the substances necessary for manufacturing include highly flammable gases. Consequently, there exists a risk of an explosive atmosphere forming.
Explosion protection concept
UHP pressure transducers for such processes must be made with the corresponding safety. As well as their small design and specific process connections, the models WUC-1x and WU-2x have a thorough explosion protection concept. The marking of the instruments provides home elevators this:
II 3G Ex ec ic IIC T6/T5/T4 Gc X
The abbreviations listed inside them mean, in more detail:
II 3G:
Equipment group 2 (all areas except mining), can be utilized in zone 2 (rare and short-term Ex atmosphere).
Ex ec ic:
Ignition protection types ?ec? (increased safety) and ?ic? (intrinsically Bonanza ).
?Ex ec? has replaced the ignition protection type ?Ex nA? (non-sparking) because the start of 2022. However, this will not affect the Ex idea of the instruments.
IIC:
Explosion group (here: gases, resistive ignition energy of 40 �J, ideal for hydrogen/acetylene).
T6/T5/T4:
Temperature classes. T6 as the highest requirement means a maximum permissible surface temperature in the Ex environment < 85 �C (max. surface temperature of the WUC-1x and WU-2x: 40 �C).
Gc:
?Equipment Protection Level? (EPL) for zone 2 per IEC 60079-0
X:
Specific requirements which are listed in the operating instructions (for example, the best mating connector).
?ec? may be the leading ignition protection type
It really is noticeable that the marking contains two ignition protection types. However, only 1 is relevant for the electrical connection: the best ignition protection type. In the case of the pressure transducers from the WU series, this can be a Ex ec (Ex nA up to 2022) mentioned first rather than the stricter Ex ic. This can also be observed in the bond values in the info sheet and operating instructions. Only Legendary of the maximum supply voltage UN = 30 V, which is also stated in the IECEx certificate, is relevant here.
What does the classification ?Ex ic? stand for? It only pertains to the potentiometer of the transducer. The resistive component has an intrinsically safe circuit and will therefore be adjusted to improve zero drift during operation. In their overall form, the WU models do not require an intrinsically safe circuit. However, they need to never be disconnected from the circuit during operation or when an Ex atmosphere exists.
Note
Further information on the WUC-1x and WU-2x UHP pressure transducers and on the subject of hydrogen can be found on the WIKA website. Should you have any questions, your contact will gladly help you.